seminar report on 33 11kv substation
#1

INDUSTRIAL TRAINING FOR DIPLOMA 3rd YEAR IN 33/11KV SUBSTRATION
Reply
#2
33/11 KV Sub Station

Main Equipments in 33 KV Sub-Station

1) Power transformer
2) Circuit breaker
3) Isolator
4) Earthing switch
5) lightning arrestor
6) Busbar
7) Current transformer
8) Potential transformer
9) Protective relay
10) DC battery set
11)Capacitor bank
12)Fire fighting system

Power transformer

Transformer is used to step down the voltage from 33 kv voltage to 11kv voltage .
Generally 3.15 MVA, 5 MVA, 10 MVA 33/11kv, Δ / Y transformer are used in 33/11kv s/s.

Maintenance of Transformers

Check Oil level in main tank & OLTC tank.
Check the color of silica gel in breather ;it must be blue in color .if it is turned pink then recondition it or replace it.
Check On load Tap Changer Lower/Raise trail by Local & Remote.
Trip trail by draining oil in Buchholz relay
Check Earth resistance ,provide watering arrangement for earthling pits.
Tight all connections.
Check breakdown voltage of oil.
Clean the bushings.
Attend the oil leakages
Note Temperature of Oil & leakage.

TRANSFORMER OIL

It’s mineral oil obtained by refine crude petroleum. It serves the following purpose.
Provide additional insulation.
Carries away the heat generated in the core & coils.
Protects the paper from dirt & moisture.

Current Transformer

Current T/F is used for protection and metering purposes.
It steps down the current level of the line for following purposes.
1) Measurement : ammeter , kw meter , kwh meter , power factor meter
2) control and protection : current when exceeds the set value operates the relay which senses the faulty condition .

Potential Transformer (P.T)

It steps down the voltage level of line for -
1) Measurement : voltmeter, frequency meter ,kw meter, kwh meter ,power factor meter
2) Control & protection : used in directional over current protection and under frequency relay operation (48.8 Hz , df/dt relay)

Circuit Breaker

Circuit Breaker can switch automatically during normal and abnormal conditions . during faulty condition the fault is sensed by the relay and operates the circuit breaker to isolate the fault.
In 33kv substation generally vacuum circuit breaker are used where are quenching medium is vacuum

Advantage of Vacuum Circuit Breaker

1) no oil is required for are quenching
2) least maintenance
3) compact size
4) light in weight
Maintenance of circuit breaker
1) close/trip through local/remote control
2) trip trial through auto closer relay
4) oiling & greasing of moving parts
5) vermin proofing
6) heater healthy

Reference: http://studentbank.in/report-33-11-kv-su...z3GlhiSeY6
Reply

Important Note..!

If you are not satisfied with above reply ,..Please

ASK HERE

So that we will collect data for you and will made reply to the request....OR try below "QUICK REPLY" box to add a reply to this page
Popular Searches: paruthipara substation industrial report, 33 11kv full topic pdf, substation technical seminar pdf, tecnical report on 33 11kv substation, seminar report substation automation, 110 kv substation project report, technical seminar projects topics on substation,

[-]
Quick Reply
Message
Type your reply to this message here.

Image Verification
Please enter the text contained within the image into the text box below it. This process is used to prevent automated spam bots.
Image Verification
(case insensitive)

Possibly Related Threads...
Thread Author Replies Views Last Post
  seminar topics on cfd ppt and full report pdf 1 21,985 02-05-2018, 06:48 PM
Last Post: hello990
  seminar report on 3d solar cells ppt paper presentation ppt seminars report on 3d solar cells ppt paper presentation ppt 5 42,533 15-04-2018, 08:39 AM
Last Post: Guest
  report on yii framework seminar 2 1,358 02-01-2018, 03:32 PM
Last Post: dhanabhagya
  seminar ppt on nanotechnology in horticulture with respect to fruit science 6 3,187 16-08-2017, 10:45 AM
Last Post: jaseela123d
  33 11kv substation ppt 5 7,673 24-07-2017, 04:28 PM
Last Post: jaseela123d
  seminar report on public safety application enabled gps smartphone and android operating system 5 2,024 26-04-2017, 10:36 AM
Last Post: jaseela123d
  seminar report on wingate vpn 1 930 15-04-2017, 02:06 PM
Last Post: jaseela123d
  seminar money pad the future wallet wikipedia 1 1,146 13-04-2017, 12:19 PM
Last Post: jaseela123d
  seminar report on epidermal electronics systems 1 835 12-04-2017, 03:18 PM
Last Post: jaseela123d
  tubular skylight report for seminar 1 795 12-04-2017, 11:07 AM
Last Post: jaseela123d

Forum Jump: