On-Line Detection Of Shorts In Fields Of Turbine Generator Rotor
#1

hi.....plz post more information regarding the above mentioned topic........

raviteja
Reply
#2
The field windings in the rotor of a generator are generally an annular array of conductive coil bars arranged in slots around the outer periphery of the rotor. A connected pair of coil bars and end turns form a coil winding turn. The coil bars extend longitudinally along the length of the rotor and are connected by end turns at each end of the rotor. Several coil winding turns make up a pole. A rotor may have multiple poles.
shorted turns: The insulation separating the conductor bars or end turns of an above described type rotor may break down and cause a short circuit across one or more coils of the winding. They are called shorted turns.It can cause overheating conditions and related vibration problems.

Methodology
A flux probe sensor is introduced in the air-gap which generates a signal proportional to the rate of change of the electromagnetic flux in the air-gap.The signal from flux probe during on-line operation is monitored, the signal is integrated to generate a flux density data trace that repeats during each rotor revolution; one cycle of the flux density signal is segmented and upon detecting a variation in the repeating flux density trace, capturing the flux probe signal data during a rotor revolution period; the steps of monitoring, integrating and capturing flux data as the on-line operation progresses through various machine load, are repeated.

Reduction and analysis of the flux probe data is triggered based on the locations of the flux density zero-crossings. Automating data collection reduces generator offline periods. To reduce the amount of data stored, the processor may be programmed to capture, the flux probe data when the zero-crossing point of the flux density trace shifts from one region to another.Data sufficient to identify a shorted turn is collected by capturing flux data each time the zero-crossing timing changes. the processor is programmed to compare the amplitudes of the coils of the different poles of the flux probe signal in the time regions aligned with the flux density zero crossing. The current captured flux data is flagged by the processor as indicating a possible shorted coil turn in a given pole.

detailed seminar report download:
[attachment=607]
Reply
#3
thanks .for the information
Reply
#4
Hi friend,
hope you liked our site. Do tell your friends about it and visit again!
Cheers
Reply
#5
Got this one late! This pdf is about online detection of shorted turns:
[attachment=1110]
Reply
#6
[attachment=5541]
GENERATOR FIELD WINDING SHORTED TURN DETECTION TECHNOLOGY



EFFECTS OF SHORTED TURNS IN ROTOR WINDINGS

The impact of operating a round rotor generator with rotor winding shorted turns depends upon many factors1. If the percentage of total turns shorted out is small, the generator may be able to run at rated load for years without further problems. However, larger shorted turn percentages can cause operating conditions that may limit unit loads. If the problems become severe, forced outages may occur. Conditions that may result in running a rotor with shorted-turns include:
1. Rotor unbalance that varies with field current changes (thermal sensitivity).
Coils with shorted-turns operate at lower temperatures than coils without shorted-turns. This is because the heating resulting from I2R losses are lower in the effected coil (the coil current is traversing a shorter copper path, therefore the coil resistance is lower), while the cooling circuits remain the same. A rotor temperature gradient that can give rise to rotor bowing will be a function of the number of turn-shorts and their location (FIGURE 1 and 2), as well as the total field current. At higher field currents, any rotor temperature gradient due to shorted turns will be greater.


Shorted-turns in coils near the quadrature axis in 2-pole rotors will have little effect on thermal sensitive balance because the effected slots are nearly 180° apart (FIGURE 1). Shorted-turns in the small coils (1, 2 or 3) of one pole will have a greater effect in causing rotor unbalance problems since the asymmetrical location will result in a larger rotor temperature gradient.
Shorted turns in 4-pole rotors will also act to produce a thermal gradient (FIGURE 2). However, since 4-pole rotors tend to be stiffer than 2-pole rotors, thermal gradients tend to be less effective in producing rotor bowing.
2. Rotor / Stator vibration due to unbalanced magnetic force.
Shorted-turns in 4-pole rotors can also cause unbalanced magnetic forces. Shorted turns in 2-pole rotors do not generally cause an unbalanced magnetic force since the reduction in magnetic flux will affect both the north and south poles equally. In 4-pole rotors, however, shorted turns in one pole will reduce the flux generated for the pole and to a lesser extent the adjacent poles, but will have no effect on the opposite pole. The resulting unbalanced radial magnetic pull between the rotor and stator can cause vibrations. The vibrations would effect both the rotor and stator at a frequency of once per revolution.
3. Higher field current is required than previously experienced at a specific load.

When shorted-turns occur, higher field current is required to maintain a specific load. This is because the same rotor amp-turns must be generated with fewer active turns. Excitation capacity may limit load if greater than 5-10% of the field winding is shorted out. Decreased efficiency will result in any case.
The Amp vs. Field-Turn relationship is AS = ANTN/TS, where AS and TS are the field current and active turns in a rotor with shorted-turns and AN and TN are the same in a rotor with no shorted-turns. The field winding loss (I2R) at a specific load can be determined by noting that the resistance of the field winding will decrease by TS/TN, but the I2 component increases by (TN/TS) 2. This results in an increase in the field winding loss of (TN/TS) for a specific load.
For example, a rotor with 2 turn shorts out of 100 (TN/TS = 100/98 = 1.02) will increase the field losses by 2%.
4. Higher field currents result in higher operating temperatures.
The higher field currents required to maintain a given load will result in an increase in I2R loss for the entire rotor winding. As a result of this higher I2R loss, the total heat generated by the field will be increased when compared to operating at the same load factors without shorted turns. However, units which make use of Volts/Amp field temperature instrumentation will falsely indicate lower operating temperatures after the onset of shorted turns. This is a result of the instrumentation algorithm used to calculate field temperature assuming a constant field resistance at any given temperature. In fact, shorted turns will reduce the total field resistance, which will be interpreted by the instrumentation as a drop in temperature.
Winding temperature rise above cold gas is proportional to I2. As an example, two turns shorted out of a total of 100 turns will result in a 4% higher hot-spot rise over cold gas. TABLE 1 shows an example at full load for a rotor with 2% and 10% shorted-turns.
Reply

Important Note..!

If you are not satisfied with above reply ,..Please

ASK HERE

So that we will collect data for you and will made reply to the request....OR try below "QUICK REPLY" box to add a reply to this page
Tagged Pages: online detection of shorts in fields of turbine generator rotor pdf,
Popular Searches: wound rotor motor inverter, rotor hover fluent, turbine rotor eccentricity, francis turbine bnabt in hindits, grid rotor resistance starter wiki, turbine technology in car, chip fields,

[-]
Quick Reply
Message
Type your reply to this message here.

Image Verification
Please enter the text contained within the image into the text box below it. This process is used to prevent automated spam bots.
Image Verification
(case insensitive)

Possibly Related Threads...
Thread Author Replies Views Last Post
  A New Data Mining Based Network Intrusion Detection Model prem0597 2 4,248 04-05-2018, 09:42 PM
Last Post: Guest
  home appliance turbine pdf ppt 2 1,149 14-08-2017, 05:25 PM
Last Post: Chetan44799
  mini ir radar for unauthorized object detection 3 1,146 15-04-2017, 03:11 PM
Last Post: jaseela123d
  automatic timetable generator source code vb 1 7,700 07-04-2017, 12:31 PM
Last Post: jaseela123d
  code to extract brain tumor detection using matlab 2 1,081 17-10-2016, 04:32 PM
Last Post: girish123ak
  matlab code for retinal hemorrhage detection in fundus images 2 866 24-08-2016, 01:10 AM
Last Post: [email protected]
  source code for suspicious email detection in java Parvesh.2595 2 1,039 23-08-2016, 04:05 PM
Last Post: seminar report asees
  automatic streetlight on off with sms controlling and failure detection with indication 2 743 22-07-2016, 02:52 PM
Last Post: jaseela123d
  code to extract brain tumor detection using matlab 2 804 21-07-2016, 10:47 AM
Last Post: jaseela123d
  wireless ac power 230v line electrical appliances controlling system 2 828 15-07-2016, 02:14 PM
Last Post: jaseela123d

Forum Jump: