hi am rabeena..i would like to know about under frequency relay
Reply
#2
Underfrequency Protective Relay

The underfrequency relay (fig. 4-16) is a solidstate device that functions to protect the load in the event generator frequency decreases below preset limits. It actuates when the frequency decreases to 55 hertz for 60-hertz operation and 46 hertz for 50-hertz operation. Upon actuation, contacts within the relay close to signal the annunicator and open to de-energize the generator breaker (contactor), resulting in a display of the fault condition and removal of the load from the generator.

Frequency sensing is accomplished by a tuned circuit consisting of capacitors C1 and C2 and components in the encapsulated base. Zener diodes CR1, CR2, and CR3 limit the peak voltage to the tuned circuit. The ac output of the tuned circuit is rectified by diode CR4 and applied to a voltage divider consisting of resistors R1, R2, R3, and R4. Transistor Q1 compares the voltage at the wiper of potentiometer R3 with the reference voltage established by zener diode CR7. When transistor Q1 conducts, transistor 42 operates as a switch to control the coil voltage on a relay contained in the encapsulated base. Both transistors Q1 and Q2 and the relay in the encapsulated base are energized when the frequency of the input voltage to terminals 1 and 2 is normal frequency (50 to 60 hertz). When an underfrequency condition occurs, the voltage at the base of transistor Q1 is not sufficient for conduction. This causes the relay to be de-energized and its contacts to switch. The underfrequency trip point is adjusted by potentiometer R3.


Appliances in India are designed to operate at 50Hz...if this is not maintained they will damage drawing high currents...
In case of faults or high loads...
power delivered by generator increases --> power input is constant (mechanical)
So the extra power comes from the kinetic enery stored in rotor --> Speed decreases
frequency tends to "fall"

So in order to maitain the frequency the extra load or fault has to be isolated for which under frequency relays are used...They work automatically.
Reply

Important Note..!

If you are not satisfied with above reply ,..Please

ASK HERE

So that we will collect data for you and will made reply to the request....OR try below "QUICK REPLY" box to add a reply to this page
Popular Searches: under relay and over relay ppt, effect of under frequency on generating units ppt, ppt on under frequency relay download, intel 8085 for under voltage relay, under frequency relay wikipedia, effect of under frequency on generating units in ppt, under voltage relay simulation in simulink,

[-]
Quick Reply
Message
Type your reply to this message here.

Image Verification
Please enter the text contained within the image into the text box below it. This process is used to prevent automated spam bots.
Image Verification
(case insensitive)

Possibly Related Threads...
Thread Author Replies Views Last Post
  effect of avenue trees on temperature under canopy and outside project 0 1,071 20-10-2018, 01:12 PM
Last Post: Guest
  relay performance testing with high technology pdf 0 2,141 20-08-2018, 10:35 PM
Last Post: Guest
  frequency measurement using 74c926 ic 0 444 24-07-2018, 12:03 PM
Last Post: Guest
  vaa21 relay manual 0 673 18-06-2018, 06:03 PM
Last Post: Guest
  areva make cdg61 relay manual pdf 0 499 07-05-2018, 12:43 AM
Last Post: Guest
  soft frequency reuse lte matlab source codes 1 493 04-03-2018, 12:35 AM
Last Post: Guest
  frequency of ac with help of sonometer practical readings 1 596 25-01-2018, 12:36 PM
Last Post: dhanabhagya
  study of effect of avenue trees on temperature under canopy and outside 1 1,227 01-01-2018, 03:52 PM
Last Post: dhanabhagya
  determining frequency by ac sonometer 1 478 27-12-2017, 09:04 AM
Last Post: jaseela123d
  8051 software program for overcurrent relay 2 525 07-11-2017, 11:22 AM
Last Post: jaseela123d

Forum Jump: