Transformers Internal Incipient Fault Model
#1

Internal winding faults resulting from the degradation of transformer winding insulation can be catastrophic and hence expensive. In the new environment of deregulation, utilities therefore are needing inexpensive methods employed to detect such faults in the incipient stage. The development of an accurate internal fault diagnostic technique for transformers must be based on analysis of quantities from faults scenarios. Considering the safety of personal, the damage that will occur in the transformer, the consumed time, and related cost, simulation involving the modeling of transformers at various incipient fault stages is the best way to generate these fault cases. In this paper, the method used contains a degrading insulation model and a transformer internal short circuit fault model. Since deteriorating insulation involves two stages aging and arcing, the degrading insulation model is composed of an aging model and an arcing model connected in parallel. The degrading insulation model was combined with internal short circuit model, to simulate internal winding incipient faults. The transformer internal incipient fault model was implemented using commercially available finite element analysis software. Various incipient fault scenarios at different degrading levels of the transformer winding insulation were simulated. In these fault scenarios, the terminal voltages and currents of the transformer were analysed in both time domain and frequency domain. The characteristics obtained from the simulation were compared with the characteristics obtained from some experimental fault cases that conveyed incipient like behaviour.
Reply
#2
can u please send d whole copy, it can be very helpful for me..
thanks in advance..
Reply
#3
see http://ieeexplore.ieeexpl/freeabs_all.js...ber=997926

[attachment=56]
[attachment=57]
Abstract
Incipient fault detection in transformers can provide early warning of electrical failure and could prevent catastrophic losses. To develop transformer incipient fault detection technique, a transformer model to simulate internal incipient faults is required. This paper presents a methodology to model internal incipient winding faults in distribution transformers. These models were implemented by combining deteriorating insulation models with an internal short circuit fault model. The internal short circuit fault model was developed using finite element analysis. The deteriorating insulation model, including an aging model and an arcing model connected in parallel, was developed based on the physical behavior of aging insulation and the arcing phenomena occurring when the insulation was severely damaged. The characteristic of the incipient faults from the simulation were compared with those from some potential experimental incipient fault cases. The comparison showed the experimentally obtained characteristic's of terminal behavior of the faulted transformer were similar to the simulation results from the incipient fault models
Reply
#4
Presented by:
MANAS ANKIT DATTA

[attachment=12944]
INTRODUCTION :
Incipient fault detection in transformer can provide early warning of electric failure and could prevent catastrophic losses. To develop transformer incipient fault detection technique a transformer model to simulate internal incipient fault is required. The model for such an operation was implemented by combining deteriorating insulation model with an internal short circuit model . The internal short circuit model was developed using finite element analysis.
The deteriorating model includes an aging and an arching model connected in parallel .
The characteristics of the incipient fault from the simulation were compared with with those from some potential experimental incipient fault cases
INDEX TERMS :
1. Distribution transformer
2. Finite element analysis
3. Aging
4. Arching
5. Internal incipient winding fault
6. modeling
DISTRIBUTION TRANSFORMER
Transformer are essential and important part of power systems. Online condition monitoring of transformer can provide early warning of electric failure and avoid catastrophic losses . However the implementation of existing monitoring methods tend to cost too much when applied to distribution transformer .A study shows that 70-80% of failures are caused by failure between turns. Therefore an online fault detection method was developed for distribution transformer that utilizes terminal behaviors of transformer
To make an accurate diagnostic decision , transformer internal winding must be characterized by analyzing quantity of data which could be generated through computer simulation or field experiments.
Finite Elemental Analysis
The finite elemental method is a numerical method to obtain approximate solutions to boundary value problems of mathematical physics . It has become a very important tool to solve electromagnetic problems because of it’s ability to model geometrically and compositionally complex problems.
Using finite elemental analysis to solve problem 3 stages
1. Meshing the problem space into contiguous element of suitable property and assigning appropriate value to material parameters
2. Model has to be excited to set up initial conditions
Specify the boundary conditions
There are 2 methods to couple finite element model with circuit equations
1. Direct coupling ( circuit equations are directly incorporated into field equations and solved simultaneously)
2. Indirect coupling(circuit simulation and coupling between field and circuit model are handled separately)
Transformer model using FEA
The 2D Magneto static solver was in Maxwell package was used to compute mutual and leakage inductance and export an equivalent circuit in format of SPICE sub circuits.
The normal transformer illustrated in fig 1 was modeled in the solver.
Simulation results :
Based on simulation system in above figure , the normal case and some fault cases were simulated . For a normal transfer model the RMS value of terminal voltages and currents from the simulation and the calculated expected results were almost equal.
Aging of transformer winding :
Aging of insulation is temporal function of temperature , the quantity of humidity and oxygen .with the help of advanced manufacturing process humidity and oxygen can be reduced. Since the temperature distribution is uneven, hot spot temperatures can have devastating effects.
In considering electric behavior of dielectric material it’s convenient to follow equivalent parallel circuit as shown above.
Arching in transformer winding
An arc is defined as a continuous luminous discharge of electricity across an insulating medium usually accompanied with partial volatilization of electrodes.
The above figure shows the simple case of arching current and voltage in a resistive load circuit.
The dotted line is the arching current, solid line is arching voltage , the dash dot line is the system voltage.
Internal incipient winding fault :
S1 and S2 are time controlled switches. If there is no arching in the circuit, S1 is closed and S2 is open and the value of E is zero. When E equals E(m) the model represents arching .when S1 is closed and S2 is open arching is in burning period .when S1 is open and S2 is closed arching is in extinction period.
Parallel combination model for insulation
The above figure represents the combinational model. The parallel model represents a perfect insulation when S1 and S2 are open , the value of e is zero and R(pm) is a very large resistance so that current in the insulation is almost zero. To represent deteriorating insulation R(pm) is decreased to a small value. When the random square wave E is zero , S1 and S2 are open. The model represents the non arching deteriorating insulation . When the value of e is E(m) , the model represents degrading insulation with arching. In this case when S1 is closed and S2 is open, the model simulates the burning period. If S1 is open and S2 is closed it models the extinction period.
Reply
#5
for internal fault we rely on DGA analysis for power transformer,tan delta ,furan etc. But for distribution transformer
which parameters can be watched,analysed which are economical..?
Reply
#6
Modeling of Transformers withInternal starting problems
The internal windings errors that occur as a result of the degradation of
transformer winding insulation can becatastrophic and therefore more expensive. In the new environment of deregulation, utility areneeding cheap, therefore, the methods used for the detection of such defects in the initial development stage.The precise diagnostic of the internal circuit of the transformer must be based onanalysis of failure scenarios.Considering the security of the individual, the damage that will occur in the transformer, consumed the time and costs involved, modeling with simulations of transformers at various early stages of faults is the best way to generate these error cases.In this article, the method used includes degrading isolation model adventurer transformer internal short-circuit fault model. Since the deterioration of the insulation is a two-step process of aging and the formation of the arc, the model degradinginsulation consists of models of ageing and ARC models connected in parallel. Thedegrading isolation model was combined with internal short circuit model, simulate the internal windingincipient faults.The internal model of the transformer incipient faults was implemented using commercial availablefinite element analysis software. Various incipient fault scenarios in various humiliating thetransformer winding insulation levels were simulated.In these scenarios, troubleshooting, Terminal voltages and currents of the transformer analyzed in the bothtime domain and the frequency domain.The characteristics, obtained from the simulations were compared with the characteristics of the received experimental cases of malfunctions fromsome that is emerging as a behavior.
Reply

Important Note..!

If you are not satisfied with above reply ,..Please

ASK HERE

So that we will collect data for you and will made reply to the request....OR try below "QUICK REPLY" box to add a reply to this page
Popular Searches: chemistrt model of 9 claas, modeling transformers internal incipient faults ppt, report pdf on transformers, how to make the model of transformers, bm model, a project report on intelligent power sharing of transformers with fault detection, working model of transformers,

[-]
Quick Reply
Message
Type your reply to this message here.

Image Verification
Please enter the text contained within the image into the text box below it. This process is used to prevent automated spam bots.
Image Verification
(case insensitive)

Possibly Related Threads...
Thread Author Replies Views Last Post
  Modelling of Transformers with Internal Incipient Faults computer science crazy 2 2,744 16-03-2015, 02:17 PM
Last Post: seminar report asees
  Fault Locating In Undegrounded And High Resistance GroundedSystems computer science crazy 12 14,719 15-04-2013, 02:15 PM
Last Post: Guest
  CONDITION MONITORING OF TRANSFORMERS full report smart paper boy 4 3,345 22-02-2013, 02:23 PM
Last Post: seminar details
  TRANSMISSION LINE FAULT MONITORING seminar class 2 3,600 13-01-2013, 10:29 PM
Last Post: [email protected]
Bug Selecting Transformers For Hydro Power Plants seminar projects crazy 1 3,611 17-12-2012, 01:48 PM
Last Post: seminar details
  Modelling of Transformers with Internal Incipient Faults computer science technology 1 3,617 30-10-2012, 03:19 PM
Last Post: seminar details
  Earthling transformers For Power systems computer girl 0 835 07-06-2012, 11:16 AM
Last Post: computer girl
  AUTOCONFIGURING ARTIFICIAL NEURAL NETWORK APPLIED TO FAULT DIAGNOSIS IN POWER SYSTEMS computer science technology 1 2,297 06-02-2012, 11:54 AM
Last Post: seminar addict
  FAULT LOCATION IN EHV TRANSMISSION LINES USING ARTIFICIAL NEURAL NETWORKS full report project topics 2 3,681 12-12-2011, 10:01 AM
Last Post: seminar addict
  Identifying Transformer Incipient Events for Maintaining Distribution System seminar class 0 1,536 09-05-2011, 12:02 PM
Last Post: seminar class

Forum Jump: