gas insulated transmission lines full report
#1

[attachment=2362]

INTRODUCTION

Composed of pipes that houses conductors in SF6
Invented in 1974
Both overhead & underground system
Drawbacks of XLPE lead to GIL
Most economic, environment friendly & maintenance free alternative



WHY GIL

Installation expense is less
XLPE needs extra cooling arrangement
Allowed conductors to be larger in cross-section
Construction of large capacity transmission link



SUPERIOR PROPERTIES OF SF6 GAS

High dielectric strength at lower cost
Regeneration capacity following a breakdown
Low pressure-increase following a breakdown
High load transfer capacity

INSTALLATION

Ground level
Elevated above ground
Below grade in an open or covered trench
Directly buried underground
Vertically in tunnels, shafts or towers
Suspended from existing substation structures

MAIN COMPONENTS

Conductors & enclosures
Insulators & particle traps
Plug in contacts
Aluminum bellows
Enclosure joints

HOW TO REDUCE THE COST OF GIL

Standardization of components
Optimization of pipeline
Introduction of N2

ADVANTAGES OF SF6-N2 MIXTURE

Less harm to atmosphere
Reduced cost for GIL
Useful for long distance power transmission
Insulating property is improved


H-GIL

Large capacity.
For long distance power transmission line.
Structure between that of GIL & XLPE.
Uses 3 sub-conductors.
Covered with solid dielectric polyethylene.
Insulated with SF6.
More flexible.
Withstands voltage same or more than GIL.
ADVANTAGES
High current carrying capacity
Limited working space
High efficiency
Low resistive & capacitive loss
Good appearance
No interference with communication circuits
No extra cooling is required
High reliability

DISADVANTAGES

Length of is each GIL section is limited.
Particle contamination lower the insulating reliability of GIL.
Breakdown of insulator.
Earthquake resistant design must be considered.
SF6 gas is harmful to ozone.


APPLICATIONS

Installation in tunnels
Ideal for environments that are sensitive to electro-magnetic fields.
Suitable for metropolitan areas where high energy rate is required.
Well suited for high power transmission.


CONCLUSION

One of the best transmission system in the world
Safe and reliable for more than 20 years
Researches are still going on to improve efficiency
Reply
#2
sir ,with due respect it is to state that i am not getting full report and ppt of GIS please plz send me the thread regarding this seminar plz


thank you so much in adv.
Reply
#3
superior technology and excellentknowhow ensure quality and reliability
Siemens GIL systems are based on thesuccessful SF6 tubular conductor technology,which has been around for severaldecades. GIL consist of a central aluminumconductor with a typical electrical crosssection of up to 5,300 mm2. The conductorrests on cast resin insulators, which centerit within the outer enclosure. This enclosureis formed by a sturdy aluminum tube,which provides a solid mechanical andelectrotechnical containment for the system.To meet up-to-date environmentaland technical aspects, GIL are filled withan insulating gas mixture of mainly nitrogenand a smaller percentage of SF6. Forincreased lifetime, the “performance line”product series has a longitudinal particletrap installed over the entire horizontalroute section. An automated orbitalwelding procedure, accompanied bytailored ultrasonic inspection techniques,ensures perfect gastightnessof the aluminum tubes.During service, the fully encapsulateddesign fully protects the GIL againstenvironmental influences. Thanks to thetechnologically clear-cut, logical designand the use of high-quality materials,an absolutely maintenance-free productis achieved which requires externalinspection only. And at the end of itsservice life, the issue of de-installationis solved. The GIL tubular system withall its components and the insulationgas mixture are 100 percent recyclable.These factors help to minimize lifetimecosts.
Impressive practical record: GIL systemin Germany’s Wehr power plant
Siemens installed a GIL in a tunnel inthe Wehr pumped-storage power stationin the Black Forest as long ago as 1975.With a single-phase length of almost 4 kmthis installation is still a significant referenceamong worldwide GIL projects. Notwithstandingits service time, an inspectionafter 30 years showed that all componentswere still in top condition, and assuredthe customer that GIL will provide manymore years of reliable operation.


download full report
http://energy.siemenshq/pool/hq/power-tr.../GIL_e.pdf
Reply
#4
pls send me thic presentation which will helps me alot.......
Reply
#5
to get information about the topic gas insulated transmission lines full report ,ppt and related topic refer the page link bellow

http://studentbank.in/report-gas-insulat...ull-report

http://studentbank.in/report-gas-insulat...4#pid64664

http://studentbank.in/report-gas-insulat...ort?page=3

http://studentbank.in/report-gas-insulat...7#pid40017

http://studentbank.in/report-gas-insulat...?pid=27634
Reply
#6
to get information about the topic gas insulated transmission lines full report ,ppt and related topic refer the page link bellow

http://studentbank.in/report-gas-insulat...ull-report

http://studentbank.in/report-gas-insulat...4#pid64664

http://studentbank.in/report-gas-insulat...ort?page=3

http://studentbank.in/report-gas-insulat...7#pid40017

http://studentbank.in/report-gas-insulat...?pid=27634
Reply
#7
(21-02-2010, 07:35 AM)project report tiger Wrote:
INTRODUCTION

Composed of pipes that houses conductors in SF6
Invented in 1974
Both overhead & underground system
Drawbacks of XLPE lead to GIL
Most economic, environment friendly & maintenance free alternative



WHY GIL

Installation expense is less
XLPE needs extra cooling arrangement
Allowed conductors to be larger in cross-section
Construction of large capacity transmission link



SUPERIOR PROPERTIES OF SF6 GAS

High dielectric strength at lower cost
Regeneration capacity following a breakdown
Low pressure-increase following a breakdown
High load transfer capacity

INSTALLATION

Ground level
Elevated above ground
Below grade in an open or covered trench
Directly buried underground
Vertically in tunnels, shafts or towers
Suspended from existing substation structures

MAIN COMPONENTS

Conductors & enclosures
Insulators & particle traps
Plug in contacts
Aluminum bellows
Enclosure joints

HOW TO REDUCE THE COST OF GIL

Standardization of components
Optimization of pipeline
Introduction of N2

ADVANTAGES OF SF6-N2 MIXTURE

Less harm to atmosphere
Reduced cost for GIL
Useful for long distance power transmission
Insulating property is improved


H-GIL

Large capacity.
For long distance power transmission line.
Structure between that of GIL & XLPE.
Uses 3 sub-conductors.
Covered with solid dielectric polyethylene.
Insulated with SF6.
More flexible.
Withstands voltage same or more than GIL.
ADVANTAGES
High current carrying capacity
Limited working space
High efficiency
Low resistive & capacitive loss
Good appearance
No interference with communication circuits
No extra cooling is required
High reliability

DISADVANTAGES

Length of is each GIL section is limited.
Particle contamination lower the insulating reliability of GIL.
Breakdown of insulator.
Earthquake resistant design must be considered.
SF6 gas is harmful to ozone.


APPLICATIONS

Installation in tunnels
Ideal for environments that are sensitive to electro-magnetic fields.
Suitable for metropolitan areas where high energy rate is required.
Well suited for high power transmission.


CONCLUSION

One of the best transmission system in the world
Safe and reliable for more than 20 years
Researches are still going on to improve efficiency

Reply
#8
[/size][/size]
(19-08-2010, 02:05 PM)arvinder Wrote: sir ,with due respect it is to state that i am not getting full report and ppt of GIS please plz send me the thread regarding this seminar plz


thank you so much in adv.

Reply
#9

(21-02-2010, 07:35 AM)project report tiger Wrote:
INTRODUCTION

Composed of pipes that houses conductors in SF6
Invented in 1974
Both overhead & underground system
Drawbacks of XLPE lead to GIL
Most economic, environment friendly & maintenance free alternative



WHY GIL

Installation expense is less
XLPE needs extra cooling arrangement
Allowed conductors to be larger in cross-section
Construction of large capacity transmission link



SUPERIOR PROPERTIES OF SF6 GAS

High dielectric strength at lower cost
Regeneration capacity following a breakdown
Low pressure-increase following a breakdown
High load transfer capacity

INSTALLATION

Ground level
Elevated above ground
Below grade in an open or covered trench
Directly buried underground
Vertically in tunnels, shafts or towers
Suspended from existing substation structures

MAIN COMPONENTS

Conductors & enclosures
Insulators & particle traps
Plug in contacts
Aluminum bellows
Enclosure joints

HOW TO REDUCE THE COST OF GIL

Standardization of components
Optimization of pipeline
Introduction of N2

ADVANTAGES OF SF6-N2 MIXTURE

Less harm to atmosphere
Reduced cost for GIL
Useful for long distance power transmission
Insulating property is improved


H-GIL

Large capacity.
For long distance power transmission line.
Structure between that of GIL & XLPE.
Uses 3 sub-conductors.
Covered with solid dielectric polyethylene.
Insulated with SF6.
More flexible.
Withstands voltage same or more than GIL.
ADVANTAGES
High current carrying capacity
Limited working space
High efficiency
Low resistive & capacitive loss
Good appearance
No interference with communication circuits
No extra cooling is required
High reliability

DISADVANTAGES

Length of is each GIL section is limited.
Particle contamination lower the insulating reliability of GIL.
Breakdown of insulator.
Earthquake resistant design must be considered.
SF6 gas is harmful to ozone.


APPLICATIONS

Installation in tunnels
Ideal for environments that are sensitive to electro-magnetic fields.
Suitable for metropolitan areas where high energy rate is required.
Well suited for high power transmission.


CONCLUSION

One of the best transmission system in the world
Safe and reliable for more than 20 years
Researches are still going on to improve efficiency

Reply

Important Note..!

If you are not satisfied with above reply ,..Please

ASK HERE

So that we will collect data for you and will made reply to the request....OR try below "QUICK REPLY" box to add a reply to this page
Popular Searches: e h v transmission lines, abstract for gas insulated transformer, gas insulated transmission lines full report, seminar on gas insulated sunstation, seminar paper on gas insulated substations, gas insulated ebook, ieee based gas insulated substations,

[-]
Quick Reply
Message
Type your reply to this message here.

Image Verification
Please enter the text contained within the image into the text box below it. This process is used to prevent automated spam bots.
Image Verification
(case insensitive)

Possibly Related Threads...
Thread Author Replies Views Last Post
  Transparent electronics full report seminar surveyer 8 24,558 04-04-2018, 07:54 AM
Last Post: Kalyani Wadkar
  wireless charging through microwaves full report project report tiger 90 70,961 27-09-2016, 04:16 AM
Last Post: The icon
  Wireless Power Transmission via Solar Power Satellite full report project topics 32 50,423 30-03-2016, 03:27 PM
Last Post: dhanabhagya
  surge current protection using superconductors full report computer science technology 13 26,986 16-03-2016, 12:03 AM
Last Post: computer science crazy
  paper battery full report project report tiger 57 61,966 16-02-2016, 11:42 AM
Last Post: Guest
  IMOD-Interferometric modulator full report seminar presentation 3 11,442 18-07-2015, 10:14 AM
Last Post: [email protected]
  digital jewellery full report project report tiger 36 66,698 27-04-2015, 01:29 PM
Last Post: seminar report asees
  LOW POWER VLSI On CMOS full report project report tiger 15 22,284 09-12-2014, 06:31 PM
Last Post: seminar report asees
  eddy current brake full report project report tiger 24 33,586 14-09-2014, 08:27 AM
Last Post: Guest
  dense wavelength division multiplexing full report project reporter 3 4,532 16-06-2014, 07:00 PM
Last Post: seminar report asees

Forum Jump: